Condensate Recovery
Plate Heat Exchanger with Secondary Control Valve
A plate heat exchanger with secondary control valve:
Component Descriptions
| Part | Component | Function |
|---|---|---|
| 1 | Isolation valve | to isolate the installation from the steam supply |
| 2 | Separator | to protect the installation from wet steam |
| 3 | Strainer | to protect the control valve from detritus |
| 4 | Hi-limit Control Valve | to protect the installation from overtemperature |
| 5 | Pressure Gauge | to monitor the steam supply pressure |
| 6 | Pressure Reducing Valve | to reduce pressure to the system |
| 7 | Pressure Gauge | to monitor the reducing valve set pressure |
| 8 | Safety Valve | to protect the downstream equipment from overpressure |
| 9 | Electronic Controller | to signal the control valve to move position |
| 10 | Pneumatic Actuator | to drive the control valve |
| 11 | E/P Positioner | to position the valve correctly at all loads |
| 12 | Vacuum Breaker | to assist condensate removal from the heater at stall conditions |
| 13 | Air Vent | to vent air from the heat exchanger steam supply |
| 14 | Isolation Valve | to isolate the air vent & vacuum breaker from the steam supply |
| 15 | Hi-limit Sensor | to sense the secondary water for overtempertaure |
| 16 | Pneumatic Actuator | to drive the control valve |
| 17 | Electronic Controller | to signal the control valve to move position |
| 18 | Temperature Sensor | to sense the secondary water for temperature |
| 19 | Isolation Valve | to isolate the secondary flow from the 3 way control valve |
| 20 | 3 Way Control Valve | to mix the secondary return with the heat exchanger flow |
| 21 | Balancing Valve | to balance the flow in the bypass with the heat exchanger |
| 22 - 27 inc. | Separator Steam Trap Set | |
| 28 | Hi-limit Cut Out | to close the hi-limit valve shut on overtemperature |
| 29 - 34 inc. | Heat Exchanger Steam Trap Set | |
| 35 | Isolation Valve | to isolate the secondary return from the heat exchanger |
| 36 | Temperature Sensor | to sense the secondary water temperature |
| 37 | Isolation Valve | to monitor the set pressure of the reducing valve |
| 38 | Control Valve | to regulate the steam flow to the heat exchanger |
| 39 | Pressure Gauge | to monitor the pressure to the heat exchanger |
| 40 | E/P Positioner | to position the valve correctly at all loads |
| 41 | Plate Heat Exchanger | to heat the secondary liquid |
Table of Parts
| Part | Component | Bronze | Cast iron | SG iron | Steel | Stainless steel | Product details | |
|---|---|---|---|---|---|---|---|---|
| 5, 7, 37 | Pressure Gauge | 100 mm Diameter Pressure Gauge with 'U' or Ring Syphon Pipes | Pressure Gauges & Temperature Gauges | |||||
| 20 | Control Valve (water) | QL73M | QL43M | Control Valves | ||||
| 11, 38 | Positioner | SP200 Electropneumatic Positioner | Positioners, Controllers & Sensors | |||||
| 10, 16 | Pneumatic Actuator | PN9000 Series Pneumatic Actuator | Pneumatic Actuators | |||||
| 36 | Control Valve (steam) | KE71 | KE71B | Control Valves | ||||
| 8 | Safety Valve | SV615 | SV73 | Safety Valves | ||||
| 9, 17 | Electronic Controller | SX25, SX75 Series Controller | Positioners, Controllers & Sensors | |||||
| 2 | Separator | S2 | S1 | S5 | Separators & Insulation Jackets | |||
| 1, 35 | Bellows Sealed Stop Valve | A3S | Bellows Sealed Stop Valves | |||||
| 3, 25, 31 | Strainer | Fig 12 | Fig 12 | Fig 14 | Fig 16 or 16L | Strainers & Filters | ||
| 6 | Pressure Reducing Valve | DP27 | Pressure Reducing & Surplussing Valves | |||||
| 13 | Air Vent | AV13 | AVC32 | Air Vents & Air Eliminators | ||||
| 12 | Vacuum Breaker | VB14 | VB21 | Vacuum Breakers | ||||
| 4 | Control Valve | SB, KA51, KC51 or KB51 | KC31, KA31 or KB31 | Self-acting Controls or Control Valves | ||||
| 27 | High Limit Cut-out | HL10 High Limit Cut-out | Self-acting Controls | |||||
| 15 | Control System | Type 130 Control System | Control Valves | |||||
| 18, 34 | Temperature Sensor | EL2200 Temperature Sensor | Control Valves | |||||
| 23, 30 | Lift Check Valve | LCV1 | LCV2 | Check Valves | ||||
| 14, 19, 22, 26, 28, 32, 33 | Ball Valve (Screwed or Flanged) | M10 | M10 | Ball Valves | ||||
| 24, 30 | Ball Float Steam Trap with Monitor | IFT14 | Steam Trap Performance Monitoring | |||||
| 39 | Plate Heat Exchanger | Ball Valves | ||||||
| 21 | Balancing Valve | BSA1T | BSA2T | BSA3T | BSA6T | Bellows Sealed Stop Valves | ||
What do I do now?
Spirax Sarco have experienced engineers available to offer advice on these applications:
Let us help you size and select these products
Arrange a visit to your plant by Spirax Sarco
Ask us a question about this application