We use cookies to give you the best experience on our website. If you continue without changing your cookie settings, we assume that you consent to our use of cookies on this device. You can change your cookie settings at any time but if you do, you may lose some functionality on our website. More information can be found in our Privacy Policy

Dampftechnologie Mit Zukunft
Capabilities Header

Quick Launch

Luft-Heizregister mit Temperaturregelung ohne Hilfsenergie

Recommended installation for a temperature controlled heater battery or unit heater.

Self-Acting Air Heater Battery Control System

Beschreibung der Bauteile

Teil Bauteil Funktion
1 Isolating Valve to isolate the installation from the steam supply
2 Strainer to protect the control valve from detritus
3 Control Valve to regulate the steam flow to the battery
4 Temperature Controller to regulate the valve position
5 Wall Mounting Bracket to fix the temperature sensor to a wall
6 - 10 inc. Steam Supply Trap Set
11 Strainer (angled) to protect the float trap from detritus
12 Ball Float Steam Trap to remove condensate from the battery
13 Drain Trap to drain the battery of condensate on shut down
14 Check Valve to prevent condensate backfeeding into the battery
15 Isolating Valve to isolate the trap set for maintenance purposes
16 Vacuum Breaker to help remove condensate during stall conditions
17 Isolating Valve
 

Tabelle der Bauteile

Teil Bauteil Bronze Grauguss SG iron Stahl Edelstahl Produktdetails
1, 6, 10, 15 Isolating Valve Globe Type HV3 A3S HV3 Stop Valves or Bellows Sealed Stop Valves
Piston Type RP31 Piston Valves
Ball Type M10 M10 Ball Valves
2, 7 'Y' Type Strainer Fig 1 or 12 Fig 12SG Fig 14 Fig 16 or 16L Strainers & Filters
3 Control Valve SB, KA51 or KB51 KA31 or KB31 Control Valves
4 Self-acting Control Type SA121 or SA128 sensor and actuator Self-acting Controls
5 Wall Mounting Bracket To suit sensor type SA121 or SA128 Self-acting Controls
8, 12 Ball Float Steam Trap IFT14 Ball Float Steam Traps
9, 14 Check Valve LCV1 LCV2 Check Valves
11 Angle Type Strainer Fig 4 or 6 Strainers & Filters
13 Drain Trap No. 8 Fixed Temperature Discharge Steam Traps
16 Vacuum Breaker VB14 VB21 Vacuum Breakers
17 Isolating Valve M10 M10 Ball Valves