We use cookies to give you the best experience on our website. If you continue without changing your cookie settings, we assume that you consent to our use of cookies on this device. You can change your cookie settings at any time but if you do, you may lose some functionality on our website. More information can be found in our Privacy Policy

Dampftechnologie Mit Zukunft
Capabilities Header

Quick Launch

Plattenwärmetauscher mit Ausgleichsventil in Sekundärseite

A plate heat exchanger with a secondary balancing valve

Plate Heat Exchanger with Balancing Valve

Beschreibung der Bauteile

Teil Bauteil Funktion
1 Isolation valve to isolate the installation from the steam and condensate systems
2 Separator to protect the installation from wet steam
3 Strainer to protect the control valve from detritus
4 Control Valve to protect the installation from overtemperature
5 Pressure Gauge to monitor the reducing valve set pressure
6 Reducing Valve to reduce pressure to the system
7 Pressure Gauge to monitor the reducing valve set pressure
8 Safety Valve to protect the downstream equipment from overpressure
9 Electronic Controller to signal the control valve to move position
10 Pneumatic Actuator to drive the control valve
11 E/P Positioner to position the valve correctly at all loads
12 Vacuum Breaker to release condensate in vacuum conditions
13 Air Vent to vent air from the pump system automatically
14 Ball Valve to isolate the various systems
15 Plate Heat Exchanger to heat the secondary fluid from steam in the primary circuit
16 Hi Limit Control System to control the hi-limit shut-off valve
17 Ball Valve to isolate the various systems
18 Hi-limit Cut-out to close the hi-limit valve shut on overtemperature
19 Isolation Valve to isolate the installation from the steam and condensate systems
20 Control Valve to regulate the flow of steam to the heat exchanger
21 Pressure Gauge to monitor the reducing valve set pressure
22 Balancing Valve to regulate the flow in the secondary balance line
23 Ball Valve to isolate the various systems
24 Ball Valve to isolate the various systems
25 Lift Check Valve to prevent backflow in the separator drain line
26 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
27 Strainer to protect the control valve from detritus
28 Ball Valve to isolate the various systems
29 Ball Valve to isolate the various systems
30 Lift Check Valve to prevent backflow in the separator drain line
31 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
32 Strainer to protect the control valve from detritus
33 Ball Valve to isolate the various systems
34 Temperature Sensor to sense the secondary water temperature
 

Tabelle der Bauteile

Teil  Bauteil Bronze Grauguss SG Eisen Stahl Edelstahl Produktdetails
5, 7, 21 Pressure Gauge 100 mm Diameter Pressure Gauge with 'U' or Ring Syphon Pipes Pressure Gauges & Temperature Gauges
11 Positioner SP200 Electropneumatic Positioner Positioners, Controllers & Sensors
10 Pneumatic Actuator PN9000 Series Pneumatic Actuator Pneumatic Actuators
20 Control Valve KE71 KE71B Control Valves
8 Safety Valve SV615 SV73 Safety Valves
9 Electronic Controller SX25, SX75 Series Controller Positioners, Controllers & Sensors
2 Separator S2 S1 S5 Separators & Insulation Jackets
1, 19 Bellows Sealed Stop Valve A3S Bellows Sealed Stop Valves
3, 27, 32 Strainer Fig 12 Fig 12 Fig 14 Fig 16 or 16L Strainers & Filters
6 Pressure Reducing Valve DP27 Pressure Reducing & Surplussing Valves
13 Air Vent AV13 AVC32 Air Vents & Air Eliminators
12 Vacuum Breaker VB14 VB21 Vacuum Breakers
4 Control Valve SB, KA51, KC51 or KB51 KC31, KA31 or KB31 Self-acting Controls or Control Valves
18 High Limit Cut-out HL10 High Limit Cut-out Self-acting Controls
16 Control System Type 130 Control System Control Valves
34 Temperature Sensor EL2200 Temperature Sensor Control Valves
25, 30 Lift Check Valve LCV1 LCV2 Check Valves
14, 17, 23, 24, 28, 29, 33 Ball Valve (Screwed or Flanged) M10 M10 Ball Valves
26, 31 Ball Float Steam Trap with Monitor IFT14 Steam Trap Performance Monitoring
15 Plate Heat Exchanger Ball Valves
22 Balancing Valve BSA1T BSA2T BSA3T BSA6T Bellows Sealed Stop Valves