We use cookies to give you the best experience on our website. If you continue without changing your cookie settings, we assume that you consent to our use of cookies on this device. You can change your cookie settings at any time but if you do, you may lose some functionality on our website. More information can be found in our Privacy Policy

Dampftechnologie Mit Zukunft
Capabilities Header

Quick Launch

Plattenwärmetauscher mit aktiver Kondensatableitung

A plate heat exchanger with heat recovery and reactive drainage:Plate Heat Exchanger with Active Drainage System

Beschreibung der Bauteile

Teil Bauteil Funktion
1 Isolation valve to isolate the installation from the steam and condensate systems
2 Separator to protect the installation from wet steam
3 Pressure Gauge to monitor the reducing valve set pressure
4 Control Valve to protect the installation from overtemperature
5 Reducing Valve to reduce pressure to the system
6 Pressure Gauge to monitor the reducing valve set pressure
7 Air Regulator to supply the positioner with air at the correct pressure
8 Electronic Controller to signal the control valve to move position
9 Isolation Valve to isolate the installation from the steam and condensate systems
10 Pneumatic Actuator to drive the control valve
11 E/P Positioner to position the valve correctly at all loads
12 Control Valve to regulate the flow of steam to the heat exchanger
13 Safety Valve to protect the downstream equipment from overpressure
14 Pressure Gauge to monitor the reducing valve set pressure
15 Plate Heat Exchanger to heat the secondary fluid from steam in the primary circuit
16 Hi Limit Control System to control the hi-limit shut-off valve
17 Temperature Sensor to sense the secondary water temperature
18 Ball Valve to isolate the various systems
19 Disc Check Valve to prevent backflow of fluid
20 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
21 Strainer to protect the control valve from detritus
22 Ball Valve to isolate the various systems
23 Hi-limit Cut-out to close the hi-limit valve shut on overtemperature
24 Ball Valve to isolate the various systems
25 Strainer to protect the control valve from detritus
26 Ball Valve to isolate the various systems
27 Disc Check Valve to prevent backflow of fluid
28 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
29 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
30 Ball Valve to isolate the various systems
31 Automatic Pump to remove condensate under stall conditions
32 Disc Check Valve to prevent backflow of fluid
33 Air Vent to vent air from the pump system automatically
34 Isolation Valve to isolate the installation
35 Disc Check Valve to prevent backflow of fluid
36 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
37 Disc Check Valve to prevent backflow of fluid
38 Ball Valve to isolate the various systems
39 Pressure Gauge to monitor the reducing valve set pressure
40 Ball Valve to isolate the various systems
 

Tabelle der Bauteile

Teil   Bauteil Bronze Grauguss SG iron Stahl Edelstahl Produktdetails
6, 14, 39 Pressure Gauge PG Pressure Gauge with 'U' or Ring Syphon Pipes Pressure Gauges & Temperature Gauges
7 Air Filter / Regulator Spirax Monnier MPC2 High Efficiency Filter/Regulator Air Set Filter/Regulators
11 Positioner SP200 Electropneumatic Positioner Positioners, Controllers & Sensors
10 Pneumatic Actuator PN9000 Series Pneumatic Actuator Pneumatic Actuators
12 Control Valve KE73 KE43 Control Valves
13 Safety Valve SV73 SV607 SV74, SV604 SVL606 Safety Valves
8 Electronic Controller SX25, SX75 Series Controller Positioners, Controllers & Sensors
2 Separator S3 S5, S7 S6, S8 Separators & Insulation Jackets
1, 9, 34 Bellows Sealed Stop Valve BSA1 BSA2 BSA3 Bellows Sealed Stop Valves
3, 21, 25 Strainer (flanged) Fig 3 Fig 33 Fig 37 Fig 34 Fig 36 Strainers & Filters
5 Pressure Reducing Valve DP27 Pressure Reducing & Surplussing Valves
4 Control Valve KA33 or KB33 KA43, KB43 or KC43 Control Valves
23 High Limit Cut-out HL10 High Limit Cut-out Self-acting Controls
16 Control System Type 130 Control System Control Valves
19 High Limit Cut-Out HL10 High Limit Cut-Out Self-acting Controls
18 Control System Type 130 Control System Self-acting Controls
17 Temperature Sensor EL2200 Temperature Sensor Control Valves
18, 22, 24, 26, 30, 38, 40 Ball Valve M10 or M20 M10 or M20 Ball Valves
20, 28, 29, 36 Ball Float Steam Trap with Monitor IFT53 IFT57 IFT54 Steam Trap Performance Monitoring
19, 27, 32, 35, 37 Disc Check Valve DCV2, 3 or 4 Check Valves
33 Air Vent AV13 AVC32 Air Vents & Air Eliminators
31 Automatic Pump MFP14 Automatic Pump Pressure Powered Pumps
15 Plate Heat Exchanger Ball Valves