Intercambiadores de calor

Intercambiador de calor de placas con válvula de equilibrado

Intercambiador de calor con válvula de equilibrado.

Intercambiador de calor de placas con válvula de equilibrado
 

Component Descriptions

Part Component Function
1 Isolation valve to isolate the installation from the steam and condensate systems
2 Separator to protect the installation from wet steam
3 Strainer to protect the control valve from detritus
4 Control Valve to protect the installation from overtemperature
5 Pressure Gauge to monitor the reducing valve set pressure
6 Reducing Valve to reduce pressure to the system
7 Pressure Gauge to monitor the reducing valve set pressure
8 Safety Valve to protect the downstream equipment from overpressure
9 Electronic Controller to signal the control valve to move position
10 Pneumatic Actuator to drive the control valve
11 E/P Positioner to position the valve correctly at all loads
12 Vacuum Breaker to release condensate in vacuum conditions
13 Air Vent to vent air from the pump system automatically
14 Ball Valve to isolate the various systems
15 Plate Heat Exchanger to heat the secondary fluid from steam in the primary circuit
16 Hi Limit Control System to control the hi-limit shut-off valve
17 Ball Valve to isolate the various systems
18 Hi-limit Cut-out to close the hi-limit valve shut on overtemperature
19 Isolation Valve to isolate the installation from the steam and condensate systems
20 Control Valve to regulate the flow of steam to the heat exchanger
21 Pressure Gauge to monitor the reducing valve set pressure
22 Balancing Valve to regulate the flow in the secondary balance line
23 Ball Valve to isolate the various systems
24 Ball Valve to isolate the various systems
25 Lift Check Valve to prevent backflow in the separator drain line
26 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
27 Strainer to protect the control valve from detritus
28 Ball Valve to isolate the various systems
29 Ball Valve to isolate the various systems
30 Lift Check Valve to prevent backflow in the separator drain line
31 Ball Float Steam Trap with Monitor to remove condensate as and when it forms
32 Strainer to protect the control valve from detritus
33 Ball Valve to isolate the various systems
34 Temperature Sensor to sense the secondary water temperature
Arrow Top
 

Table of Parts

Part   Component Bronze Cast iron SG iron Steel Stainless steel Product details
5, 7, 21 Pressure Gauge 100 mm Diameter Pressure Gauge with 'U' or Ring Syphon Pipes Pressure Gauges & Temperature Gauges
11 Positioner SP200 Electropneumatic Positioner Positioners, Controllers & Sensors
10 Pneumatic Actuator PN9000 Series Pneumatic Actuator Pneumatic Actuators
20 Control Valve     KE71 KE71B   Control Valves
8 Safety Valve SV615 SV73       Safety Valves
9 Electronic Controller SX25, SX75 Series Controller Positioners, Controllers & Sensors
2 Separator   S2 S1 S5   Separators & Insulation Jackets
1, 19 Bellows Sealed Stop Valve       A3S   Bellows Sealed Stop Valves
3, 27, 32 Strainer Fig 12   Fig 12 Fig 14 Fig 16 or 16L Strainers & Filters
6 Pressure Reducing Valve     DP27     Pressure Reducing & Surplussing Valves
13 Air Vent AV13     AVC32   Air Vents & Air Eliminators
12 Vacuum Breaker VB14       VB21 Vacuum Breakers
4 Control Valve SB, KA51, KC51 or KB51 KC31, KA31 or KB31       Self-acting Controls or Control Valves
18 High Limit Cut-out HL10 High Limit Cut-out Self-acting Controls
16 Control System Type 130 Control System Control Valves
34 Temperature Sensor EL2200 Temperature Sensor Control Valves
25, 30 Lift Check Valve LCV1     LCV2   Check Valves
14, 17, 23, 24, 28, 29, 33 Ball Valve (Screwed or Flanged)       M10 M10 Ball Valves
26, 31 Ball Float Steam Trap with Monitor     IFT14     Steam Trap Performance Monitoring
15 Plate Heat Exchanger           Ball Valves
22 Balancing Valve   BSA1T BSA2T BSA3T BSA6T Bellows Sealed Stop Valves