Heat Exchangers
Plate Heat Exchanger with Condensate Level Control
Heat exchanger with constant steam pressure and condensate level control valve.
Component Descriptions
| Part | Component | Function |
|---|---|---|
| 1 | Isolation valve | to isolate the installation from the steam supply |
| 2 | Separator | to protect the installation from wet steam |
| 3 | Strainer | to protect the control valve from detritus |
| 4 | Hi-limit Control Valve | to protect the installation from overtemperature |
| 5 | Pressure Gauge | to monitor the steam supply pressure |
| 6 | Pressure Reducing Valve | to reduce pressure to the system |
| 7 | Pressure Gauge | to monitor the reducing valve set pressure |
| 8 | Safety Valve | to protect the downstream equipment from overpressure |
| 9 | Isolation Valve | to monitor the set pressure of the reducing valve |
| 10 | Vacuum Breaker | to assist condensate removal from the heater at stall conditions |
| 11 | Air Vent | to vent air from the heat exchanger steam supply |
| 12 | Isolation Valve | to isolate the air vent & vacuum breaker from the steam supply |
| 13 - 17 inc. | Separator Steam Trap Set | |
| 18 | Hi-limit Cut Out | to close the hi-limit valve shut on overtemperature |
| 19 | Hi-limit Sensor | to sense the secondary water for overtempertaure |
| 20 | Temperature Sensor | to sense the secondary water for temperature |
| 21 | Isolation Valve | to isolate the secondary flow from the heat exchanger |
| 22 | Electronic Controller | to signal the control valve to move position |
| 23 | Pneumatic Actuator | to drive the control valve |
| 24 | E/P Positioner | to position the valve correctly at all loads |
| 25 | Balancing Valve | to balance the flow in the bypass with the heat exchanger |
| 26 | Isolation Valve | to isolate the secondary return from the heat exchanger |
| 27 - 32 inc. | Heat Exchanger Steam Trap Set | |
| 33 | Plate Heat Exchanger | to heat the secondary liquid |
Table of Parts
| Part | Component | Bronze | Cast iron | SG iron | Steel | Stainless steel | Product details | |
|---|---|---|---|---|---|---|---|---|
| 5, 7 | Pressure Gauge | 100 mm Diameter Pressure Gauge with 'U' or Ring Syphon Pipes | Pressure Gauges & Temperature Gauges | |||||
| 24 | Positioner | SP200 Electropneumatic Positioner | Positioners, Controllers & Sensors | |||||
| 23 | Pneumatic Actuator | PN9000 Series Pneumatic Actuator | Pneumatic Actuators | |||||
| 29 | Control Valve | KE71 | KE71B | Control Valves | ||||
| 8 | Safety Valve | SV615 | SV73 | Safety Valves | ||||
| 22 | Electronic Controller | SX25, SX75 Series Controller | Positioners, Controllers & Sensors | |||||
| 2 | Separator | S2 | S1 | S5 | Separators & Insulation Jackets | |||
| 1, 9 | Bellows Sealed Stop Valve | A3S | Bellows Sealed Stop Valves | |||||
| 3, 16, 31 | Strainer | Fig 12 | Fig 12 | Fig 14 | Fig 16 or 16L | Strainers & Filters | ||
| 6 | Pressure Reducing Valve | DP27 | Pressure Reducing & Surplussing Valves | |||||
| 11 | Air Vent | AV13 | AVC32 | Air Vents & Air Eliminators | ||||
| 10 | Vacuum Breaker | VB14 | VB21 | Vacuum Breakers | ||||
| 4 | Control Valve | SB, KA51, KC51 or KB51 | KC31, KA31 or KB31 | Self-acting Controls or Control Valves | ||||
| 18 | High Limit Cut-out | HL10 High Limit Cut-out | Self-acting Controls | |||||
| 19 | Control System | Type 130 Control System | Control Valves | |||||
| 20 | Temperature Sensor | EL2200 Temperature Sensor | Control Valves | |||||
| 14, 28 | Lift Check Valve | LCV1 | LCV2 | Check Valves | ||||
| 12, 13, 17, 21, 26, 27, 32 | Ball Valve (Screwed or Flanged) | M10 | M10 | Ball Valves | ||||
| 33 | Plate Heat Exchanger | Ball Valves | ||||||
| 25 | Balancing Valve | BSA1T | BSA2T | BSA3T | BSA6T | Bellows Sealed Stop Valves | ||
Hvad gør jeg nu?
Spirax Sarco have experienced engineers available to offer advice on these applications:
Let us help you size and select these products
Få en aftale med Spirax Sarco om et besøg på dit anlæg
Ask us a question about this application