Component Descriptions

Part Component Function
1 Isolation Valve to isolate the trap set from the supply steam
2 Strainer to protect the trap from detritus
3 Spiratec Sensor Chamber to monitor the trap condition
4 Thermodynamic Steam Trap to discharge condensate correctly
5 Balanced Pressure Steam Trap to discharge condensate correctly
6 Inverted Bucket Steam Trap to discharge condensate correctly
7 Sight Glass to observe the condensate condition
8 Check Valve to prevent reverse flow
9 Isolation Valve to isolate the trap set from the condensate system
Arrow Top
 

Table of Parts

Part   Component Bronze Cast iron SG iron Steel Stainless steel Product details
1, 9 Isolating Valve Globe Type HV3     A3S   HV3 Stop Valves or Bellows Sealed Stop Valves
Piston Type       RP31   Piston Valves
Ball Type       M10 M10 Ball Valves
2 Strainer Fig 1 or 12 Fig 13 Fig 12SG Fig 14 Fig 16 or 16L Strainers & Filters
3* Spiratec Sensor Chamber     ST171 ST141 ST161 Steam Trap Performance Monitoring
4 Thermodynamic Steam Trap †         UTD30L Swivel Connectors & Traps
5 Balanced Pressure Steam Trap         UBP30 Swivel Connectors & Traps
6 Inverted Bucket Steam Trap †         UIB30 Swivel Connectors & Traps
7* Sight Glass † Single Window,
Double Window,
Sight Check ††
        Sight Glasses
6 Check Valve LCV1     LCV2   Check Valves

* Items 3 and 7 are not normally installed together - both are shown to indicate position.
† If item 4 or 6 is used, item 7 should be installed at least 1 metre downstream of the trap.
†† Separate Check Valve not required.

Arrow Top

What do I do now?

Spirax Sarco have experienced engineers available to offer advice on these applications:

  • Let us help you size and select these products

  • Arrange a visit to your plant by Spirax Sarco